Functions
124
7UM62 Manual
C53000-G1176-C149-3
Table 2-8
Fault Modeling and Measuring Errors on the Generator Side in Case of System
Faults
System Fault
Fault Model on the
Generator Side
Loop selection
Measuring Errors
3–pole short
circuit
3–pole short circuit
Phase-earth
Always correct
measuring
2–pole short
circuit
3–pole short circuit
Phase-earth loop
with highest current
Always correct
measuring
1–pole short
circuit
2–pole short circuit
Phase-phase loop
Impedance measured
too high by the zero
impedance
Z
G