Functions
120
7UM62 Manual
C53000-G1176-C149-3
2.16.2 Setting Hints
General
The forward active power protection is only effective and accessible if this function
was set within the framework of the protective function configuration (section 2.2,
address
,
=
Enabled
. Set
Disabled
if the function is not
required. The address
, serves to switch the function
ON
or
OFF
or to block only the trip command (
Block Relay
).
Pick-up Values
Time Delays
The setting of the forward power protection depends on the intended purpose. For this
reason, general setting instructions are not possible. The pickup values are set in
percent of the secondary apparent power rating S
Nsec
=
√
3
⋅
U
Nsec
⋅
I
Nsec
.
Consequently, the machine power must be converted to secondary quantities:
with
P
sec
secondary active power according to setting value
S
Nsec
Secondary rated power =
√3 ⋅
U
Nsec
⋅
I
Nsec
P
mach
Active power of machine according to setting value
S
N mach
Rated apparent power of machine
U
N mach
Rated voltage of machine
I
N mach
Rated current of the machine
U
N prim
Primary rated voltage of voltage transformers
I
N prim
Primary rated current of current transformers
Address
serves to set the threshold of the forward power to an underrange (
and address
(
) serves to set it to overrange. Addresses
T-Pf< and
T-Pf> serve to set the associated time delays.
In address
the user can select whether a fast or a precise
measuring procedure must be used for the forward power calculation. In most cases,
the precise measuring procedure is preferred in the power station sector (as a rule),
whereas the fast procedure is applied for use as network decoupling.
The set times are additional time delays not including the operating times (measuring
time, drop-out time) of the protective function.
2.16.2.1 Settings of the Forward Active Power Supervision
Setting
P
sec
S
Nsec
---------------
P
mach
S
N mach
--------------------
U
N mach
U
N prim
---------------------
I
N mach
I
N prim
------------------
⋅
⋅
=
=
Addr.
Setting Title
Setting Options
Default Setting
Comments
3201
FORWARD
POWER
OFF
ON
Block relay for trip com-
mands
OFF
Forward Power Supervision
3202
Pf<
0.5..120.0 %
9.7 %
P-forw.< Supervision Pickup
3204
T-Pf<
0.00..60.00 sec;
∞
10.00 sec
T-P-forw.< Time Delay
3203
Pf>
1.0..120.0 %
96.6 %
P-forw.> Supervision Pickup
3205
T-Pf>
0.00..60.00 sec;
∞
10.00 sec
T-P-forw.> Time Delay
3206A
MEAS. METHOD
Method accurate
Method fast
Method accurate
Method of Operation