Differential Protection (ANSI 87G/87M/87T)
89
7UM62 Manual
C53000-G1176-C149-3
2.12.2 Setting Hints
General
The differential protection is only effective and accessible if the type of protected
object for this function was set within the framework of the protective function
configuration (Section 2.2, address
=
Generator/Motor
or
Three-phase trans.
). Only the relevant parameters for that object are offered, all
others are hidden.
Disabled
is set if the function is not required. At the address
the user can switch the function
ON
or
OFF
, or only block the trip
command (
Block Relay
).
The primary rated current
I
p, CT
of the used CTs should normally be higher than the
rated current
I
N, Object
of the object to be protected. However, at least the following
condition should be observed with regard to the upper limit of the linear zone of the
7UM62, which is 20
⋅ Ι
N
:
2.12.2.1 Differential Protection for Generators and Motors
Precondition
A precondition for the functioning of the generator or motor differential protection is
that during configuration at the address
=
Generator/Motor
has been set.
One important setting is the location of the CT starpoints on both sides of the protected
object (addresses
for side 1 and
for side 2, see Section 2.3).
Also, the nominal values (S
N GEN/MOTOR
, U
N GEN/MOTOR
) of the machine to be
protected, and the primary and secondary nominal currents of the main CTs on both
sides must be entered. The settings are referred to these values. They are also used
e.g. for determining the primary measured values.
Information as to the treatment of the starpoint on both sides is required for the
measured value monitoring; it has already been entered during configuration at the
addresses
0241
and
0244
(see Section 2.3.2).
Increase of Pickup
Value on Startup
For additional security against overfunctioning when a non-energized protection
object is switched in, an increase of the pickup value on startup can be set at address
. On delivery of the device, this function is switched
OFF
.
The associated parameters can be found at addresses
and
Address
is used to set the pickup value for startup
detection. The function is disabled by setting I/I
nO
= 0. The
specifies
the increase factor of the pickup values on startup. For generator and motor
protection, a setting of
=
2.0
is recommended.
Note:
When the device is delivered, the differential protection function is switched
OFF
. This
is because this protection function must not be used before at least the vector groups
and matching values have been correctly set. Without these settings the device may
show unpredictable behaviour (e.g. tripping)!
I
p, CT
0.75
I
N, Object
⋅
>