2 Functions
76
7UM61 Manual
C53000-G1176-C127-3
2.10.4 Information List
1706
I2>>
10 .. 100 %
60 %
I2>> Pickup
1707
T I2>>
0.00 .. 60.00 sec;
∞
3.00 sec
T I2>> Time Delay
No.
Information
Type of In-
formation
Comments
5143
>BLOCK I2
EM
>BLOCK I2 (Unbalance Load)
5146
>RM th.rep. I2
EM
>Reset memory for thermal replica I2
5151
I2 OFF
AM
I2 switched OFF
5152
I2 BLOCKED
AM
I2 is BLOCKED
5153
I2 ACTIVE
AM
I2 is ACTIVE
5156
I2> Warn
AM
Unbalanced load: Current warning stage
5158
RM th.rep. I2
AM
Reset memory of thermal replica I2
5159
I2>> picked up
AM
I2>> picked up
5160
I2>> TRIP
AM
Unbalanced load: TRIP of current stage
5161
I2
Θ
TRIP
AM
Unbalanced load: TRIP of thermal stage
5165
I2> picked up
AM
I2> picked up
Addr.
Parameter
Setting Options
Default Setting
Comments
www
. ElectricalPartManuals
. com