2.9 Thermal Overload Protection (ANSI 49)
67
7UM61 Manual
C53000-G1176-C127-3
If the temperature input is used, the trip times change if the coolant temperature devi-
ates from the internal reference temperature of 104.00
°
F or 40
°
C. The following
formula can be used to calculate the trip time:
with
τ
TIME CONSTANT
(address
1603
)
k
K-FACTOR
(address
1602
)
I
N
Nominal Device Current
I
Actually Flowing Secondary Current
I
Pre
Previous Load Current
Θ
N
Temperature with Nominal Current I
N
(Address
1605
)
Θ
K
Coolant Temperature Input (Scaling with Address
1608
or
1609
)
Example:
Machine:
I
NMach
= 483 A
I
maxMach
= 1.15 I
N
at
Θ
K
= 40
°
C
τ
th
= 600 s (thermal time constant of the machine)
Current transformer: 500 A/1 A