3 Mounting and Commissioning
246
7UM61 Manual
C53000-G1176-C127-3
Table 3-8
Jumper setting of control voltages of binary inputs BI1 to BI8 on Input/Output
module module C– I/O–1 in the 7UM612
1)
Factory settings for devices with rated power supply voltages 24 VDC to 125 VDC
2)
Factory settings for devices with rated power supply voltages 110 VDC to 220 VDC and
115/230 VAC
3)
Use only with control voltages 220 VDC or 250 VDC
Jumpers X71, X72 and X73 on the C–I/O–1 board serve to set the bus address. The
jumpers must not be changed. The following table lists the jumper presettings.
The installation locations of the boards are shown in Figures 3-1 to 3-2 .
Table 3-9
Module address jumper setting of input/output module C-I/O-1 for 7UM612
Binary Inputs
Jumper
19 V Threshold
BI8
X21/X22
L
M
H
BI9
X23/X24
L
M
H
BI10
X25/X26
L
M
H
BI11
X27/X28
L
M
H
BI12
X29/X30
L
M
H
BI13
X31/X32
L
M
H
BI14
X33/X34
L
M
H
BI15
X35/X36
L
M
H
Jumper
Factory Setting
X71
L
X72
H
X73
H
www