2.32 RTD-Box
195
7UM61 Manual
C53000-G1176-C127-3
2.32.3 Settings
Addresses which have an appended "A" can only be changed with DIGSI, under Ad-
ditional Settings.
Addr.
Parameter
Setting Options
Default Setting
Comments
9011A
RTD 1 TYPE
Not connected
Pt 100
Ω
Ni 120
Ω
Ni 100
Ω
Pt 100
Ω
RTD 1: Type
9012A
RTD 1 LOCATION
Oil
Ambient
Winding
Bearing
Other
Winding
RTD 1: Location
9013
RTD 1 STAGE 1
-50 .. 250
°
C;
∞
100
°
C
RTD 1: Temperature Stage 1
Pickup
9014
RTD 1 STAGE 1
-58 .. 482
°
F;
∞
212
°
F
RTD 1: Temperature Stage 1
Pickup
9015
RTD 1 STAGE 2
-50 .. 250
°
C;
∞
120
°
C
RTD 1: Temperature Stage 2
Pickup
9016
RTD 1 STAGE 2
-58 .. 482
°
F;
∞
248
°
F
RTD 1: Temperature Stage 2
Pickup
9021A
RTD 2 TYPE
Not connected
Pt 100
Ω
Ni 120
Ω
Ni 100
Ω
Not connected
RTD 2: Type
9022A
RTD 2 LOCATION
Oil
Ambient
Winding
Bearing
Other
Other
RTD 2: Location
9023
RTD 2 STAGE 1
-50 .. 250
°
C;
∞
100
°
C
RTD 2: Temperature Stage 1
Pickup
9024
RTD 2 STAGE 1
-58 .. 482
°
F;
∞
212
°
F
RTD 2: Temperature Stage 1
Pickup
9025
RTD 2 STAGE 2
-50 .. 250
°
C;
∞
120
°
C
RTD 2: Temperature Stage 2
Pickup
9026
RTD 2 STAGE 2
-58 .. 482
°
F;
∞
248
°
F
RTD 2: Temperature Stage 2
Pickup
9031A
RTD 3 TYPE
Not connected
Pt 100
Ω
Ni 120
Ω
Ni 100
Ω
Not connected
RTD 3: Type
9032A
RTD 3 LOCATION
Oil
Ambient
Winding
Bearing
Other
Other
RTD 3: Location
9033
RTD 3 STAGE 1
-50 .. 250
°
C;
∞
100
°
C
RTD 3: Temperature Stage 1
Pickup