2 Functions
86
7ST6 Manual
E50417-G1176-C251-A3
2.4.3
Settings
The table indicates region-specific presettings. Column C (configuration) indicates the
corresponding secondary nominal current of the current transformer.
2.4.4
Information List
Addr.
Parameter
C
Setting Options
Default Setting
Comments
2401
HS O/C
ON
OFF
ON
High-Speed Overcurrent
Protection
2404
I HS O/C
1A
1.0 .. 25.0 A;
∞
10.0 A
High-Speed O/C Pickup
Current
5A
5 .. 125 A;
∞
50 A
2405
T HS O/C
0.006 .. 0.100 sec; 0;
∞
0.000 sec
High-Speed O/C Delay
Time
2408
HS O/C TRIP
single-channel
dual-channel
dual-channel
HS O/C TRIP Allocation
No.
Information
Type of In-
formation
Comments
4271
HS O/C OFF
OUT
HS O/C is switched OFF
4281
HS O/C PICKUP
OUT
HS O/C PICKED UP
4293
HS O/C TRIP
OUT
HS O/C TRIPPED
13815
HS O/C TRIP (M)
OUT
HS O/C TRIPPED (M)
13816
>HS O/C ON
SP
>Switch on HS O/C Protection
13817
>HS O/C OFF
SP
>Switch off HS O/C Protection
13818
HSo/c ON/OFF BI
IntSP
HS O/C ON/OFF about Binary Input
13819
HS O/C Failure
OUT
HS O/C uC-Failure