A.6 Protocol-dependent Functions
309
7ST6 Manual
E50417-G1176-C251-A3
A.6
Protocol-dependent Functions
Protocol
→
IEC 60870-5-103
PROFIBUS
FMS
PROFIBUS DP
DNP3.0
Additional
Service
Interface
(optional)
Function
↓
Operational Mea-
sured Values
Yes
Yes
Yes
Yes
Yes
Metered Values
Yes
Yes
Yes
Yes
Yes
Fault Recording
Yes
Yes
No. Only via addi-
tional service inter-
face
No. Only via ad-
ditional service
interface
Yes
Remote Protection
setting
No. Only via addi-
tional service inter-
face
Yes
No. Only via addi-
tional service inter-
face
No. Only via ad-
ditional service
interface
Yes
User-defined an-
nunciations and
switching objects
Yes
Yes
Predefined „User-
defined Annuncia-
tions“ in CFC
Predefined
„User-defined
Annunciations“
in CFC
Yes
Time Synchroniza-
tion
Via protocol;
DCF77/IRIG B;
Interface; Binary
Input
Via protocol;
DCF77/IRIG B;
Interface; Binary
Input
Via DCF77/IRIG B;
Interface; Binary
input
Via protocol;
DCF77/IRIG B;
Interface; Binary
Input
-
Messages with Time
Stamp
Yes
Yes
No
Yes
Yes
Commissioning Tools
Measured Value In-
dication Blocking
Yes
Yes
No
No
Yes
Creating test mes-
sages
Yes
Yes
No
No
Yes
Physical Mode
Asynchronous
Asynchronous
Asynchronous
Asynchronous
-
Transmission Mode Cyclically/Event
Cyclically/Event
Cyclically
Cyclically/Event -
Baud Rate
4800 to 38400
Up to 1.5 MBaud
Up to 1.5 MBaud
2400 to 19200
2400 to
115200
Type
RS 232 RS 485 fibre
optic cable
RS485 fibre optic
cable
Double ring
RS485 fibre optic
cable
Double ring
RS485 fibre
optic cable
RS232/RS48
5