2.1 General
27
7ST6 Manual
E50417-G1176-C251-A3
The following table presents an overview of the activation or blocking of functions.
Details are set out in the respective function description.
2.1.1.2
Setting Notes
Configuration of
Functional Scope
Configuration settings can be entered by using a PC and the software program DIGSI
®
and transferred via the operating interface of the device or via the service interface on
the rear. Operation using DIGSI
®
is described in the SIPROTEC
®
4 System Descrip-
tion, order no. E50417-H1176-C151.
Entry of password No. 7 (for setting modification) is required to modify configuration
settings. Without the password, the settings may be read, but may not be modified and
transmitted to the device.
The functional scope with the available options is set in the
Functional Scope
dialog
box to match plant requirements.
Special Character-
istics
Most settings are self-explaining. The special cases are described below.
If use of the setting group changeover function is desired, address
103
Grp Chge
OPTION
should be set to
Enabled
. In this case, up to four different groups of settings
may be changed quickly and easily during device operation (see also Subsection
2.1.4). Only one setting group may be selected and used if the setting is
Disabled
.
The impedance characteristic valid for distance protection is selected under address
113
DISTANCE CURVE
. You can choose between distance protection with combined
tripping characteristic and distance protection with polygonal tripping characteristic
(see Section 2.2).
The available protection and supplementary functions can be configured as
Enabled
or
Disabled
.
When ordering devices, please note that the basic device version does not offer the
full scope of functions. The table below shows which functions are provided in the
basic device version, and which must be ordered separately if required:
ON/OFF Blocking
Function
BI
SI
Para
BI
SI
Para
Distance Protection
x
-
x
x
-
-
High-Speed Overcurrent Pro-
tection
x
-
x
-
-
-
Overcurrent Protection
x
-
x
-
-
-
Emergency Overcurrent Pro-
tection
x
-
x
-
-
-
Voltage Protection
-
-
x
-
-
-
Thermal Overload Protection
x
-
x
-
-
-
Defrosting Protection
x
x
x
x
x
x
Inrush Restraint
-
-
-
-
-
-
Fault locator
-
-
-
-
-
-
Breaker Failure Protection
x
-
x
-
-
-
Trip circuit supervision
-
-
x
-
-
-
IT Function
x
-
x
-
-
-
Synchro-check x
-
x
x
-
-
Automatic Reclosure Function
x
x
x
x
-
-