4.1 General
257
7ST6 Manual
E50417-G1176-C251-A3
4.1.2
Auxiliary Voltage
DC Voltage
4.1.3
Binary Inputs and Outputs
Binary Inputs
Voltage supply via integrated converter
Rated auxiliary voltage U
Aux
DC
24/48 VDC
60/110/125 VDC
110/125/220/250 V
DC
Admissible voltage ranges
19 to 58 VDC
48 to 150 VDC
88 to 300 VDC
Admissible AC ripple voltage,
peak to peak
≤
15 % of the auxiliary voltage
Power input
- Quiescent
Approx. 5 W
- Energized
7ST6 1*
Approx. 8 W
7ST6 3*
Approx. 15 W
Plus approx. 1.5 W per interface module
Bridging time for power supply failure/short circuit
≥
50 ms at U
Aux
= 48 V and U
Aux
≥
110 V
for 7ST61 50 ms at U
Aux
= 24 V and U
Aux
= 60 V
for 7ST63
≥
25 ms at U
aux
= 24 V and
≥
30 ms at U
aux
= 60 V
Variant
Quantity
7ST61*
12 (configurable)
7ST63*
38 (configurable)
Rated voltage range
24 VDC to 250 VDC, in 3 ranges, bipolar
Switching thresholds
Adjustable with jumpers
- For rated voltages
24/48/60/110/125 VDC
U high
≥
19 VDC
U low
≤
10 VDC
- For rated voltages
110/125/220/250 VDC
U high
≥
88 VDC
U low
≤
44 VDC
- For rated voltages
220/250 VDC
U high
≥
176 VDC
U low
≤
88 VDC
Current consumption, energized
Approx. 1.8 mA
Independent of the control voltage
Maximum admissible voltage
300 VDC
Interference suppression with capacitive coupling
With an interference pulse of 200 V and a coupling capacity of
220 nF, repeat time > 60 ms
www
. ElectricalPartManuals
. com