2.16 Monitoring Function
169
7ST6 Manual
E50417-G1176-C251-A3
2.16.4 Setting Notes
Fuse Failure
Monitor
With the parameter
MEASURE. SUPERV
(address
2901
) fuse failure monitoring can
either be switched off or operated in one of the two possible operating modes. If the
parameter is set to
Without FFM
, a fuse failure (failure of the measuring voltage) is
always detected when the voltage has dropped below 5 V while at the same time an
operating current is flowing. This setting should be chosen if it has been ensured that
the short-circuit currents occurring at the device amounts to at least 1.2 In. With the
setting
Without FFM
, a fuse failure is detected with a delay of 5 s.
If this is not the case, select the setting
With FFM
. With this setting, the device also
checks whether a non-steady process is detected in the current path at the same time
as the voltage dip. In this case a fuse failure will not be detected until 10 s after the
voltage dip, provided that the currents are in the operating current range.
2.16.5 Settings
2.16.6 Information List
Addr.
Parameter
Setting Options
Default Setting
Comments
2901
MEASURE. SUPERV
With FFM
Without FFM
OFF
With FFM
Measurement Supervision
No.
Information
Type of In-
formation
Comments
169
VT FuseFail>t
OUT
VT Fuse Failure (alarm >t)
170
VT FuseFail
OUT
VT Fuse Failure (alarm instantaneous)
196
Fuse Fail M.OFF
OUT
Fuse Fail Monitor is switched OFF
197
MeasSup OFF
OUT
Measurement Supervision is switched OFF
2054
Emer. mode
OUT
Emergency mode
13953
Failure Umeas
OUT
Measured value failure: Umeas failed