2 Functions
140
7ST6 Manual
E50417-G1176-C251-A3
2.12.4 Information List
3442
2-8 Recl:Tdead
0.01 .. 1800.00 sec;
∞
0.50 sec
Dead Time for 2nd to 8th Reclo-
sure Cycle
3450
AUTO-TH-AR
ON
OFF
ON
Automatic Reclosure after
Thermal Trip
3451
No. of TH-AR
1 AR-cycle
2 AR-cycles
3 AR-cycles
4 AR-cycles
5 AR-cycles
6 AR-cycles
7 AR-cycles
8 AR-cycles
1 AR-cycle
Max. Number Automatic Reclo-
sure Attempts
3455
TInhibit TH
0.50 .. 300.00 sec
3.00 sec
Inhibit Time after Reclosure
3456
Tdead TH MAX
1 .. 60 min;
∞
30 min
Maximum Duration of Dead Time
No.
Information
Type of In-
formation
Comments
2701
>AR ON
SP
>Auto reclose ON
2702
>AR OFF
SP
>Auto reclose OFF
2703
>BLOCK AR
SP
>BLOCK Auto reclose
2710
>Th-AR block
SP
>Th-AR: Block thermal AR-function
2711
>AR Start
SP
>External start of internal Auto reclose
2718
>Th-AR ON
SP
>Th-AR: Switch on thermal-AR function
2719
>Th-AR OFF
SP
>Th-AR: Switch off thermal-AR function
2731
>Sync.release
SP
>AR: Synchronism from ext. sync.-check
2742
>BLK 1.AR-cycle
SP
>AR: Block 1st AR-cycle
2746
>Trip for AR
SP
>AR: External Trip for AR start
2781
Auto recl. OFF
OUT
Auto recloser is switched OFF
2782
Auto recl. ON
IntSP
Auto recloser is switched ON
2783
AR is blocked
OUT
AR: Auto-reclose is blocked
2784
AR is NOT ready
OUT
Auto recloser is NOT ready
2785
AR DynBlock
OUT
Auto-reclose is dynamically BLOCKED
2787
CB not ready
OUT
AR: Circuit breaker not ready
2788
AR T-CBreadyExp
OUT
AR: CB ready monitoring window expired
2793
Th-AR not rdy
OUT
Th-AR: Thermal AR not ready
2794
Th-AR off
OUT
Th-AR: Thermal AR is switched off
2795
Th-AR on
IntSP
Th-AR: Thermal AR is switched on
2796
AR on/off BI
IntSP
AR: Auto-reclose ON/OFF via BI
2801
AR in progress
OUT
Auto-reclose in progress
2805
Th-AR in prog
OUT
Th-AR: Thermal AR in progress
2808
AR BLK: CB open
OUT
AR: CB open with no trip
2809
AR T-Start Exp
OUT
AR: Start-signal monitoring time expired
2810
AR TdeadMax Exp
OUT
AR: Maximum dead time expired
2819
ThAR Tdead ru
OUT
Th-AR: dead time is running
Addr.
Parameter
Setting Options
Default Setting
Comments