2.11 InRush Restraint
123
7ST6 Manual
E50417-G1176-C251-A3
2.11.3 Settings
The table indicates region-specific presettings. Column C (configuration) indicates the
corresponding secondary nominal current of the current transformer.
2.11.4 Information List
Addr.
Parameter
C
Setting Options
Default Setting
Comments
2301
Inrush DIS >=Z2
NO
YES
NO
Distance Zones >=Z2
Blocked by Inrush
2302
Inrush O/C
NO
YES
NO
O/C Blocked by Inrush
2303
Inrush O/C BU
NO
YES
NO
Emerg. O/C Blocked by
Inrush
2305
2nd HARM.BLOCK
10 .. 45 %
15 %
2nd Harmonics Content of
Inrush Blocking
2306
Imax InrushRest
1A
0.5 .. 25.0 A
7.5 A
Max.Current, overriding
inrush restraint
5A
2.5 .. 125.0 A
37.5 A
2307
SI Time INRUSH
0 .. 10000 ms;
∞
∞
ms
Seal-In Time of Inrush De-
tection
No.
Information
Type of In-
formation
Comments
13946
INRUSH detected
OUT
Inrush detection picked up
13947
Inrush Dis ON
OUT
Inrush detection for Dis. is switched ON
13948
Inrush O/C ON
OUT
Inrush detection O/C is switched ON
13949
Inrush BuO/C ON
OUT
Inrush detection Emerg. O/C ON