2.10 Defrosting Protection
119
7ST6 Manual
E50417-G1176-C251-A3
2.10.3 Settings
The table indicates region-specific presettings. Column C (configuration) indicates the
corresponding secondary nominal current of the current transformer.
2.10.4 Information List
Addr.
Parameter
C
Setting Options
Default Setting
Comments
4301
Defrosting
ON
OFF
OFF
Defrosting Protection
4302
ID>
0.10 .. 2.00 I/In
0.40 I/In
Pickup Current ID> De-
frosting Protection
4303
T ID>
0.00 .. 30.00 sec;
∞
0.10 sec
Delay Time ID> for De-
frosting Protection
4304
k
0.00 .. 0.80
0.50
Charact. Slope of Defrost-
ing Protection
4306
IX>>
1A
0.10 .. 25.00 A;
∞
2.00 A
Pickup Current High-Set
Stage IX>>
5A
0.50 .. 125.00 A;
∞
10.00 A
4307
T IX>>
0.00 .. 30.00 sec;
∞
0.30 sec
Delay Time IX>>
4308
IX>
1A
0.10 .. 25.00 A;
∞
1.50 A
Pickup Overcurrent Stage
IX>
5A
0.50 .. 125.00 A;
∞
7.50 A
4309
T IX>
0.00 .. 30.00 sec;
∞
0.50 sec
Delay Time IX>
No.
Information
Type of In-
formation
Comments
13960
>Defrost ON
SP
>Switch on Defrosting Protection
13961
>Defrost OFF
SP
>Switch off Defrosting Protection
13962
>BLOCK Defrost
SP
>BLOCK Defrosting Protection
13963
Defrost ON
IntSP
Defrosting Protection is switched ON
13964
Defrost OFF
OUT
Defrosting Protection is switched OFF
13965
Defrost blk
OUT
Defrosting Protection is blocked
13966
Defrost PICKUP
OUT
Defrosting Protection PICKED UP
13967
Defrost TRIP
OUT
Defrosting Protection TRIP
13970
IX>> Pickup
OUT
Defrosting current IX>> Pickup
13971
IX> Pickup
OUT
Defrosting current IX> Pickup
13972
IX>> TRIP
OUT
Defrosting current IX>> TRIP command
13973
IX> TRIP
OUT
Defrosting current IX> TRIP command
13974
Diff PU
OUT
Differential Protection picked up
13975
Diff TRIP
OUT
Differential Protection TRIP
13976
DEF ON/OFF BI
IntSP
Defrosting Protection on/off about BI
13978
Defrost block
IntSP
Block Defrosting Protection