2 Functions
110
7ST6 Manual
E50417-G1176-C251-A3
2.9.2
Setting Notes
General
The circuit breaker trip supervision is one of the basic functions of the 7ST6 device.
This function cannot be disabled by a configuration parameter.
To activate the function, the indication
„>Ext. CB Trip“
(FNo. 1438) must be con-
figured to a binary input, and this binary input must be connected with the TRIP
command of the circuit breaker to be monitored.
Current Interrup-
tion
The interruption of the current flow is monitored by a current threshold
I> CB
(address
2921
). Set this current threshold to a value that is lower than the pickup values of all
overcurrent functions.
Supervision Dura-
tion
The maximum duration of the trip supervision is set with parameter
T I> CB MAX
in
address
2922
. The supervision duration begins on activation of the signal
„>Ext. CB
Trip“
(FNo.1438).
After the set supervision time
T I> CB MAX
has elapsed, a signal generated by the
trip supervision
„CB Fault“
(FNo.1491) is reset.
2.9.3
Settings
The table indicates region-specific presettings. Column C (configuration) indicates the
corresponding secondary nominal current of the current transformer.
2.9.4
Information List
Addr.
Parameter
C
Setting Options
Default Setting
Comments
2921
I> CB
1A
0.05 .. 0.50 A
0.10 A
Pickup Current Trip Super-
vision
5A
0.25 .. 2.50 A
0.50 A
2922
T I> CB MAX
1 .. 200 sec
30 sec
Maximum Duration of Trip
Supervision
No.
Information
Type of In-
formation
Comments
1438
>Ext. CB Trip
SP
>External CB Trip
1491
CB Fault
OUT
Circuit Breaker Fault