SIPROTEC 4 Devices
4-15
7SJ63 Manual
C53000-G1140-C120-1
4.4
Control
The multiple application possibilities for SIPROTEC
®
4 devices require an equally
flexible concept for command editing and control.
Remote
If the device is integrated into a control system, then command outputs can be remote-
ly controlled via the system interface using telegrams from
q
SCADA or
q
substation controller devices such as SICAM SC.
Local
On-site, the SIPROTEC
®
4 device offers the possibility to control a circuit breaker or
primary switching equipment using the HMI.
For devices with graphical displays, switching operations can be carried out using the
control display.
•
Select the primary switching equipment using the arrow keys on the control panel.
Press the
key to close the primary equipment. Press the
key to open (trip)
the primary equipment.
DIGSI
®
4
Control operations can be carried out using the DIGSI
®
4 Tool. Connect a PC to the
PC-interface at front of the device on site, or communicate with the SIPROTEC
®
de-
vice using a modem and the service interface.
DIGSI
®
4 must operate in the On-line mode for this function.
•
Select
&RQWURO
in the Navigation window and double click on
%UHDNHU
6ZLWFKHV
in the data window.
In the dialog window that follows, all relevant primary control equipment is displayed
in a table with the present status.
•
Enter the intended device position in the Scheduled column. Answer the question
with
<HV
.
The password is requested, the interlocking conditions are checked, and the com-
mand is issued.
CFC
Using the graphically supported design tool CFC for logic functions in DIGSI
®
4, infor-
mation can be logically combined. Command outputs can be derived from the output
of logic functions. The link of the output of the CFC functions to the respective device
outputs is determined in the configuration matrix.
&/26(
23(1
Note:
If the device has a key switch, the switch must be in “local” position for keypad com-
mands to be carried out.
Note:
The control option of DIGSI
®
4 is typically used during commissioning, and for test and
diagnostic purposes.