Technical Data
10-13
7SJ63 Manual
C53000-G1140-C120-1
10.3
Inverse-Time Overcurrent Protection (51 and 51N Elements)
Pickup and Time
Multiplier Ranges/
Resolutions
Pickup Current
51, 51N
0.50 A to 20.00 A
1
) (Increments 0.05 A)
1
)
Time Multipliers for
T
p
, T
Ep
0.05 s to 3.20 s
(Increments 0.01 s)
I
p
, I
Ep,
IEC–Characteristics
or
∞
(delay does not expire)
Time Multiplier for 51, 51N D
0.05 s to 15.00 s (Increments 0.01 s)
ANSI characteristics
or
∞
(delay does not expire)
Trip Time Charac-
teristics As Per IEC
As per IEC 60255-3, Section 3.5.2 or BS 142 (See also Figure 10-1)
The trip times for I/I
p
≥
20 are identical to those for I/I
p
= 20.
Pickup threshold
approx. 1.10 · I
p
Dropout threshold
approx. 1.05 · I
p
for I
p
/I
N
≥
0.3
Tolerances
Pickup Currents I
p
, I
Ep
2 % of setting value, or 50 mA
1
)
Trip Time for 2
≤
I/I
p
≤
20
5 % of reference (calculated) value + 2 %
current tolerance, respectively 30 ms
Influencing Vari-
ables for Pickup
Power supply direct voltage in range
0.8
≤
V
PS
/ V
PS nominal
≤
1.15
1 %
Temperature in range
23º F
≤
ϑ
amb
≤
131º F
0.06% /10º F
Frequency in range
0.95
≤
f/f
N
≤
1.05
1 %
Harmonic currents
– Up to 10 % 3. Harmonic
1 %
– Up to 10 % 5. Harmonic
1 %
1
) For I
N
= 1 A, divide all limits and increments by 5.
t
0.14
I I
p
⁄
(
)
0.02
1
–
----------------------------------
T
p
⋅
=
1250$/,19(56(
(Type A)
t
13.5
I I
p
⁄
(
)
1
1
–
---------------------------
T
p
⋅
=
9(5<,19(5(6(
(Type B)
t
80
I I
p
⁄
(
)
2
1
–
---------------------------
T
p
⋅
=
(;75(0(/<,19
(Type C)
t
120
I I
p
⁄
(
)
1
1
–
---------------------------
T
p
⋅
=
/21*,19(56(
(Type B)
For All Characteristics
t
trip time in seconds
T
p
setting value of the time multiplier
I
fault current
I
p
setting value of the pickup current
[s]
[s]
[s]
[s]
www
. ElectricalPartManuals