Functions
2.11 Monitoring Functions
SIPROTEC, 7SJ62/64, Manual
C53000-G1140-C207-2, Release date 01.2008
216
2.11.2.3 Settings
2.11.2.4 Information List
2.11.3
Malfunction Responses of the Monitoring Functions
In the following malfunction responses of monitoring equipment are clearly listed.
2.11.3.1 Description
Malfunction Responses
Depending on the type of malfunction discovered, an annunciation is sent, a restart of the processor system is
initiated, or the device is taken out of service. After three unsuccessful restart attempts, the device is taken out
of service. The operational readiness NC contact operates to indicate the device is malfunctioning. Also, the
red LED ”ERROR" lights up on the front cover, if the internal auxiliary voltage is present, and the green ”RUN"
LED goes out. If the internal auxiliary voltage fails, all LEDs are dark. Table 2-14 provides a summary of the
monitoring functions and the malfunction responses of the relay.
Addr.
Parameter
Setting Options
Default Setting
Comments
8201
FCT 74TC
ON
OFF
ON
74TC TRIP Circuit Supervision
8202
Alarm Delay
1 .. 30 sec
2 sec
Delay Time for alarm
No.
Information
Type of In-
formation
Comments
6851
>BLOCK 74TC
SP
>BLOCK 74TC
6852
>74TC trip rel.
SP
>74TC Trip circuit superv.: trip relay
6853
>74TC brk rel.
SP
>74TC Trip circuit superv.: bkr relay
6861
74TC OFF
OUT
74TC Trip circuit supervision OFF
6862
74TC BLOCKED
OUT
74TC Trip circuit supervision is BLOCKED
6863
74TC ACTIVE
OUT
74TC Trip circuit supervision is ACTIVE
6864
74TC ProgFail
OUT
74TC blocked. Bin. input is not set
6865
74TC Trip cir.
OUT
74TC Failure Trip Circuit