Functions
2.1 General
SIPROTEC, 7SJ61, Manual
C53000-G1140-C210-1, Release date 02.2008
40
2.1.3.3
Settings
Addresses which have an appended "A" can only be changed with DIGSI, under "Display Additional Settings".
The table indicates region-specific default settings. Column C (configuration) indicates the corresponding sec-
ondary nominal current of the current transformer.
Addr.
Parameter
C
Setting Options
Default Setting
Comments
201
CT Starpoint
towards Line
towards Busbar
towards Line
CT Starpoint
204
CT PRIMARY
10 .. 50000 A
100 A
CT Rated Primary Current
205
CT SECONDARY
1A
5A
1A
CT Rated Secondary
Current
209
PHASE SEQ.
A B C
A C B
A B C
Phase Sequence
210A
TMin TRIP CMD
0.01 .. 32.00 sec
0.15 sec
Minimum TRIP Command
Duration
211A
TMax CLOSE CMD
0.01 .. 32.00 sec
1.00 sec
Maximum Close
Command Duration
212
BkrClosed I MIN
1A
0.04 .. 1.00 A
0.04 A
Closed Breaker Min.
Current Threshold
5A
0.20 .. 5.00 A
0.20 A
214
Rated Frequency
50 Hz
60 Hz
50 Hz
Rated Frequency
217
Ignd-CT PRIM
1 .. 50000 A
60 A
Ignd-CT rated primary
current
218
Ignd-CT SEC
1A
5A
1A
Ignd-CT rated secondary
current
235A
ATEX100
NO
YES
NO
Storage of th. Replicas w/o
Power Supply
238
Ignd2-CT PRIM
1 .. 50000 A
60 A
Ignd2-CT rated primary c.
(conn. to I2)
250A
50/51 2-ph prot
ON
OFF
OFF
50, 51 Time Overcurrent
with 2ph. prot.
251A
CT Connect.
A, B, C, (Gnd)
A,G2,C,G; G->B
A,G2,C,G; G2->B
A, B, C, (Gnd)
CT Connection
260
Ir-52
10 .. 50000 A
125 A
Rated Normal Current (52
Breaker)
261
OP.CYCLES AT Ir
100 .. 1000000
10000
Switching Cycles at Rated
Normal Current
262
Isc-52
10 .. 100000 A
25000 A
Rated Short-Circuit Break-
ing Current
263
OP.CYCLES Isc
1 .. 1000
50
Switch. Cycles at Rated
Short-Cir. Curr.
264
Ix EXPONENT
1.0 .. 3.0
2.0
Exponent for the Ix-
Method
265
Cmd.via control
(Setting options depend
on configuration)
None
52 B.Wear: Open Cmd. via
Control Device