Technical Data
4.15 Automatic Reclosing System 79
SIPROTEC, 7SJ61, Manual
C53000-G1140-C210-1, Release date 02.2008
351
4.15
Automatic Reclosing System 79
Number of Reclosures
0 to 9 (segregated into phase and ground settings)
Cycles 1 to 4 can be adjusted individually
The following Protective Functions initiate the AR
79 (no 79 start / 79 start / 79 blocked)
50-3, 50-2, 50-1, 51, 50N-3, 50N-2, 50N-1, 51N,
Sensitive Ground Fault Protection, 46, Binary Inputs
Blocking of 79 by
Pickup of protective elements for which 79 blocking is set
(see above)
Three phase pickup (optional)
Binary Input
Last TRIP command after the reclosing cycles is complete
(unsuccessful reclosing)
CLOSE Command of the breake failure protection
Opening the circuit breaker without 79
External CLOSE Command
Breaker failure monitoring
Dead Time T
Dead
(separate for phase and ground and individual for
shots 1 to 4)
0.01 s to 320.00 s
Increments 0.01 s
Extension of Dead Time
Using binary input with time monitoring
Blocking Duration for Manual-CLOSE Detection
T
Blk Manual Close
0.50 s to 320.00 s or
∞
Increments
0.01 s
Blocking Duration after Manual Close T
Blocking Time
0.50 s to 320.00 s
Increments 0.01 s
Blocking Duration after Dynamic Blocking T
Blk Dyn
0.01 s to 320.00 s
Increments 0.01 s
Start Signal Monitoring Time T
Start Monitor
0.01 s to 320.00 s or
∞
Increments 0.01 s
Circuit Breaker Monitoring Time T
CB Monitor
0.10 s to 320.00 s
Increments 0.01 s
Maximum Dead Time Extension T
Dead Exten
0.50 s to 320.00 s or
∞
Increments 0.01 s
Start delay of dead time
Using binary input with time monitoring
Max. start delay of dead time T
Dead delay
0.0 s to 1800.0 s or
∞
Increments 1.0 s
Operating time T
Operat
0.01 s to 320.00 s or
∞
Increments 0.01 s
The following protection functions can be influ-
enced by the automatic reclosing function individ-
ually for the cycles 1 to 4 (setting value T=T/ in-
stantaneous T=0/ blocked T=infinite):
50-3, 50-2, 50-1, 51,50N-3, 50N-2, 50N-1, 51N
Additional Functions
Lockout (Final Trip)
Circuit breaker monitoring using breaker auxiliary contacts