Functions
2.14 Temperature Detection via RTD Boxes
SIPROTEC, 7SJ61, Manual
C53000-G1140-C210-1, Release date 02.2008
203
2.14.3
Settings
Addresses which have an appended "A" can only be changed with DIGSI, under "Display Additional Settings".
Addr.
Parameter
Setting Options
Default Setting
Comments
9011A
RTD 1 TYPE
Not connected
Pt 100
Ω
Ni 120
Ω
Ni 100
Ω
Pt 100
Ω
RTD 1: Type
9012A
RTD 1 LOCATION
Oil
Ambient
Winding
Bearing
Other
Oil
RTD 1: Location
9013
RTD 1 STAGE 1
-50 .. 250 °C;
∞
100 °C
RTD 1: Temperature Stage 1
Pickup
9014
RTD 1 STAGE 1
-58 .. 482 °F;
∞
212 °F
RTD 1: Temperature Stage 1
Pickup
9015
RTD 1 STAGE 2
-50 .. 250 °C;
∞
120 °C
RTD 1: Temperature Stage 2
Pickup
9016
RTD 1 STAGE 2
-58 .. 482 °F;
∞
248 °F
RTD 1: Temperature Stage 2
Pickup
9021A
RTD 2 TYPE
Not connected
Pt 100
Ω
Ni 120
Ω
Ni 100
Ω
Not connected
RTD 2: Type
9022A
RTD 2 LOCATION
Oil
Ambient
Winding
Bearing
Other
Other
RTD 2: Location
9023
RTD 2 STAGE 1
-50 .. 250 °C;
∞
100 °C
RTD 2: Temperature Stage 1
Pickup
9024
RTD 2 STAGE 1
-58 .. 482 °F;
∞
212 °F
RTD 2: Temperature Stage 1
Pickup
9025
RTD 2 STAGE 2
-50 .. 250 °C;
∞
120 °C
RTD 2: Temperature Stage 2
Pickup
9026
RTD 2 STAGE 2
-58 .. 482 °F;
∞
248 °F
RTD 2: Temperature Stage 2
Pickup
9031A
RTD 3 TYPE
Not connected
Pt 100
Ω
Ni 120
Ω
Ni 100
Ω
Not connected
RTD 3: Type
9032A
RTD 3 LOCATION
Oil
Ambient
Winding
Bearing
Other
Other
RTD 3: Location
9033
RTD 3 STAGE 1
-50 .. 250 °C;
∞
100 °C
RTD 3: Temperature Stage 1
Pickup