Technical Data
10-25
7SA522 Manual
C53000-G1176-C119-2
Non-Synchronous
System Conditions
∆
f-measurement
0.03 Hz to 2.00 Hz
(steps 0.01 Hz)
Tolerance
15 mHz
Threshold synchronous /
non-synchronous
0.01 Hz
Circuit-breaker operating time
0.01 s to 0.60 s
Times
Minimum measuring time
approx. 80 ms
Maximum time delay
0.01 s to 600.00 s;
∞
(steps 0.01 s)
Tolerance of all timers
1 % of set value or 10 ms
10.13 Overvoltage Protection
Phase Voltages
Measurement
voltages phase–earth
separate reference voltage U
x
Pick-up value
U
Ph
>
1.0 V to 170.0 V
(steps 0.1 V)
Delay time
T
UPh>
0.00 s to 30.00 s
(steps 0.01 s)
Drop-out to pick-up ratio
approx. 0.95
Pick-up time
approx. 30 ms
Drop-out time
approx. 30 ms
Trip command
local and/or transfer
Carrier impulse time
T
Uph>Imp
0.05 s to 0.50 s
(steps 0.01 s)
Tolerances
U
Ph
>
≤
3 % of set value or 1 V
T
UPh>
1 % of set value or 10 ms
Displacement
Voltage
Measurement
zero sequence voltage 3·U
0
Pick-up value
3U
0
>
1.0 V to 300.0 V
(steps 0.1 V)
Delay time
T
3U0>
0.00 s to 30.00 s
(steps 0.01 s)
Drop-out to pick-up ratio
0.50 to 0.95
(steps 0.01)
Pick-up time
approx. 65 ms
Drop-out time
approx. 30 ms
Trip command
local and/or transfer
Trip impulse time
T
3U0>Imp
0.05 s to 0.50 s(steps 0.01 s)
Tolerances
3U
0
>
≤
3 % of set value or 1 V
T
3U0>
1 % of set value or 10 ms
Summary of Contents for siprotec 7SA522
Page 20: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 64: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 89: ...SIPROTEC 4 Devices 4 25 7SA522 Manual C53000 G1176 C119 2 Figure 4 20 CFC Logic example ...
Page 408: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 456: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 516: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 620: ...Appendix B 48 ...