Technical Data
10-23
7SA522 Manual
C53000-G1176-C119-2
10.10 High-Current Switch-On-To-Fault Protection
Pick-up
High current pick-up
I>>>
1.00 A to 25.00 A
1
)
(steps 0.01 A)
Drop-out to pick-up ratio
approx. 0.90
Pick-up tolerance
≤
3 % of set value or 1% of I
N
Times
Shortest tripping time
approx. 13 ms
10.11 Automatic Re-closure Function
Automatic
Re-closures
Number of re-closures
max. 8,
first 4 with individual settings
Operating modes
1-pole, 3-pole or 1-/3-pole
Control
with pick-up or trip command
Action times
0.01 s to 300.00 s;
∞
Initiation possible without pick-up
(steps 0.01 s)
and action time
Different dead times before
re-closure can be set for all
0.01 s to 1800.00 s;
∞
operating modes and cycles
(steps 0.01 s)
Dead times after evolving fault
0.01 s to 1800.00 s;
recognition
(steps 0.01 s)
Reclaim time after reclosure
0.50 s to 300.00 s
(steps 0.01 s)
Blocking time after dynamic blocking 0.5
Blocking time after manual closing
0.50 s to 300.00 s ; 0
(steps 0.01 s)
Start signal monitoring time
0.01 s to 300.00 s
(steps 0.01 s)
Circuit-breaker supervision time
0.01 s to 300.00 s
(steps 0.01 s)
Adaptive Dead
Time
Operating modes
with voltage measurement or
with close command transmission
Action time
0.01 s to 300.00 s;
∞
Initiation possible without pick-up
(steps 0.01 s)
and action time
Maximum dead time
0.50 s to 3000.00 s;
∞
(steps 0.01 s)
Voltage measurement dead-line
or bus
2 V to 70 V (phase-to-earth)
(steps 1 V)
Summary of Contents for siprotec 7SA522
Page 20: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 64: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 89: ...SIPROTEC 4 Devices 4 25 7SA522 Manual C53000 G1176 C119 2 Figure 4 20 CFC Logic example ...
Page 408: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 456: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 516: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 620: ...Appendix B 48 ...