Functions
6-194
7SA522 Manual
C53000-G1176-C119-2
6.13.3 Settings
6.13.4 Information Overview
Adr.
Parameter
Setting options
Presetting
Description
3701 FCT
Uphase-e OFF
Alarm Only
ON
ON Phase-Earth
Overvoltage
function is
3702
Uph-e>
1.0..170.0 V
85.0 V
Uph-e> Pickup
3704
T Uph-e
0.00..30.00 sec
2.00 sec
T Uph-e Time Delay
3705
T Sen-Imp(Uphe)
0.05..0.50 sec
0.25 sec
Time of Carrier Send Impulse
(Uph-e)
3721 FCT
3U0(Ux) OFF
Alarm Only
ON
OFF
Zero Sequence Overvoltage (or
Ux) is
3722
3U0>
1.0..300.0 V
30.0 V
3U0> (or Ux>) Pickup
3723
3U0 Reset Ratio
0.50..0.95
0.80
3U0 (or Ux) Reset ratio
3724
T 3U0
0.00..30.00 sec
2.00 sec
T (3U0 or Ux) Time Delay
3725
T Sen-Imp 3UO
0.05..0.50 sec
0.25 sec
Time of Carrier Send Impulse
(3U0 or Ux)
F.No.
Alarm
Comments
4308
>BLOCK Uph-e
>BLOCK Phase-E Overvoltage function
4309
>BLOCK 3U0
>BLOCK Zero Seq. Overvoltage function
4315
Uph-e OFF
Overvoltage Phase-E is switched OFF
4316
Uph-e BLOCK
Overvoltage Phase-E is BLOCKED
4317
Uph-e ACTIVE
Overvoltage Phase-E is ACTIVE
4318
3U0 OFF
Zero Seq.Overvoltage is switched OFF
4319
3U0 BLOCK
Zero Seq.Overvoltage is BLOCKED
4320
3U0 ACTIVE
Zero Seq.Overvoltage is ACTIVE
4341
Uphe PICKUP
Overvoltage Phase-E PICKED UP
4342
Uphe Pickup L1
Overvoltage Phase-E PICKUP L1
4343
Uphe Pickup L2
Overvoltage Phase-E PICKUP L2
4344
Uphe Pickup L3
Overvoltage Phase-E PICKUP L3
4345
Uphe SEND
Overvoltage Ph-E Carrier SendImpulse
4350
3U0 PICKUP
Zero Seq. Overvoltage PICKED UP
4351
3U0 SEND
Zero Seq. OverV. Carrier SendImpulse
4361
Uphe TRIP
Overvoltage Phase-E TRIP command
4362
3U0 TRIP
Overvoltage Zero Seq. TRIP command
Summary of Contents for siprotec 7SA522
Page 20: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 64: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 89: ...SIPROTEC 4 Devices 4 25 7SA522 Manual C53000 G1176 C119 2 Figure 4 20 CFC Logic example ...
Page 408: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 456: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 516: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 620: ...Appendix B 48 ...