Functions
6-150
7SA522 Manual
C53000-G1176-C119-2
6.10.2 Applying the Function Parameter Settings
A prerequisite for the operation of the switch-on-to-fault protection is that in address
627)2YHUFXUU
=
(QDEOHG
was set during the configuration of the device
scope of functions (Section 5.1). It is furthermore possible to switch the function, in ad-
dress
,
627)2YHUFXUU
21
or
2))
.
The magnitude of the current which causes pick-up of the switch on to fault function is
set as
in address
. The setting value should be selected large enough to
ensure that the protection under no circumstances picks up due to an overload condi-
tion or due to a current increase resulting from e.g. an automatic reclosure dead time
on a parallel feeder. It is recommended to set at least 2.5 times the rated current of
the feeder.
6.10.3 Settings
The indicated secondary current values for setting ranges and default settings refer to
I
N
= 1 A. For the nominal current 5 A these values are to be multiplied by 5.
6.10.4 Information Overview
Addr.
Setting Title
Setting Options
Default Setting
Comments
2401
FCT SOTF-O/C
ON
OFF
ON
Inst. High Speed SOTF-O/C is
2404
I>>>
1.00..25.00 A
2.50 A
I>>> Pickup
F.No.
Alarm
Comments
4253
>BLOCK SOTF-O/C
>BLOCK Instantaneous SOTF Overcurrent
4271
SOTF-O/C OFF
SOTF-O/C is switched OFF
4272
SOTF-O/C BLOCK
SOTF-O/C is BLOCKED
4273
SOTF-O/C ACTIVE
SOTF-O/C is ACTIVE
4281
SOTF-O/C PICKUP
SOTF-O/C PICKED UP
4282
SOF O/CpickupL1
SOTF-O/C Pickup L1
4283
SOF O/CpickupL2
SOTF-O/C Pickup L2
4284
SOF O/CpickupL3
SOTF-O/C Pickup L3
4295
SOF O/CtripL123
SOTF-O/C TRIP command L123
Summary of Contents for siprotec 7SA522
Page 20: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 64: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 89: ...SIPROTEC 4 Devices 4 25 7SA522 Manual C53000 G1176 C119 2 Figure 4 20 CFC Logic example ...
Page 408: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 456: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 516: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 620: ...Appendix B 48 ...