3426 RAR T-1POL
RAR 1pole dead time
min. 0.01
s
max. 320.00
©©©©
3427 RAR T1POL2
RAR accelerated 1pole dead time (U0 dependent)
min. 0.01
s
max. 320.00
©©©©
3428 EV.F.RECOG
Evolving fault recognition with 1pole AR
WITH FAULT DETEC [ ] With fault detection
WITH TRIP COMM. [ ] With trip command
3429 EV.F.BLOCK
Blocking with evolving faults
ALWAYS
[ ] Always
NEVER
[ ] Never
>T-DISCR.
[ ] >T-discrimination
3430 T-DISCRIM
Discrimination time for evolving faults
min. 0.01
s
max. 320.00
©©©©
3431 AR TRIP 3P
3p trip when AR is blocked during 1p dead time
YES
[ ] yes
NO
[ ] no
3442 DAR PROG.
Delayed auto-reclose program
NO DAR
[ ] No DAR
DAR WITHOUT RAR [ ] DAR without RAR
DAR AFTER RAR
[ ] DAR only after RAR
3443 DAR No.1PH
Number of DAR shots after 1 pole initiation
min. 0
max. 9
©©©©
3444 DAR No.3PH
Number of DAR shots after 3 pole initiation
min. 0
max. 9
©©©©
3445 DAR T-ACT.
Delayed auto-reclose action time
min. 0.01
s
max. 320.00/Ñ
©©©©
3446 DAR T3POL1
DAR 3pole dead time for 1st shot
min. 0.01
s
max. 1800.00
©©©©
3447 DAR T3POL2
DAR 3pole dead time for 2nd shot
min. 0.01
s
max. 1800.00
©©©©
3448 DAR T3POL3
DAR 3pole dead time for 3rd and further shots
min. 0.01
s
max. 1800.00
©©©©
©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©
3500 CHECK SYNCHRONISM
3501 SYNC-CHECK
Synchro-check function
ON
[ ] on
OFF
[ ] off