$SSHQGL[
6$
9
&*&
3200 EARTHFAULT DIREC.COMPARISON
3201 E/F COMPAR
Directional comparison for E/F def. time prot
ON
[ ] on
OFF
[ ] off
3202 T-DELAY
Delay time for transmission and trip on recept
min. 0.00
s
max. 32.00/Ñ
©©©©
3203 T-TRANSBLO
Transient blocking time after external fault
min. 0.01
s
max. 32.00
©©©©
3204 T-WAIT
Waiting time for trans.block. (missing recept)
min. 0.01
s
max. 32.00/Ñ
©©©©
3210 E/F ECHO
Echo function for directional comparison
ON
[ ] on
OFF
[ ] off
3211 T-ECHO-DEL
Echo delay time
min. 0.01
s
max. 32.00/Ñ
©©©©
3212 T-ECHO-IMP
Duration of echo impulse
min. 0.02
s
max. 32.00
©©©©
3213 T-ECHO-BLO
Echo blocking time
min. 0.01
s
max. 32.00
©©©©
©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©
3300 EARTHFAULT NON-DIRECTIONAL
3301 E/F I.T.
Non directional inverse time E/F protection
ON
[ ] on
OFF
[ ] off
3302 E/F CHARAC
Trip time characteristic
NORMAL INVERSE
[ ] Normal inverse
VERY INVERSE
[ ] Very inverse
EXTREMELY INVERS [ ] Extremely inverse
3303 Ie>
Pick-up value for earth current detection
min. 0.10
I/In
max. 4.00
©©©©
3304 T-Ie>
Delay time multiplier
min. 0.00
s
max. 32.00/Ñ
©©©©
3305 T-BLOCK
Blocking time after dist.prot. has dropped off
min. 0.01
s
max. 320.00
©©©©
Summary of Contents for SIPROTEC 7SA511