1600 DIST.PROT. FAULT DETECTION
1601 Iph>>
Overcurrent detection Iph>>
min. 0.25
I/In
max. 4.00
©©©©
1602 Ie>
Earth fault detection Ie>
min. 0.10
I/In
max. 1.00
©©©©
1611 Iph>
Minimum current for fault detection Iph>
min. 0.10
I/In
max. 1.00
©©©©
1612 Uphe(I>>)
Undervoltage pick-up at I>> (phase-earth)
min. 20
V
max. 70
©©©©
1613 Uphe(I>)
Undervoltage pick-up at I> (phase-earth)
min. 20
V
max. 70
©©©©
1614 Uphph(I>>)
Undervoltage pick-up at I>> (phase-phase)
min. 40
V
max. 130
©©©©
1615 Uphph(I>)
Undervoltage pick-up at I> (phase-phase)
min. 40
V
max. 130
©©©©
1621 Iph>
Minimum current for fault detection Iph>
min. 0.10
I/In
max. 4.00
©©©©
1622 X+A
Fault detection forward reach X+A
min. 0.10
Ï
max. 200.00
©©©©
1623 X-A
Fault detection reverse reach X-A
min. 0.10
Ï
max. 200.00
©©©©
1624 RA1
Fault det. resistance (ph-ph, phi<PHI A) RA1
min. 0.10
Ï
max. 200.00
©©©©
1625 RA2
Fault det. resistance (ph-ph, phi>PHI A) RA2
min. 0.10
Ï
max. 200.00
©©©©
1626 RA1E
Fault det. resistance (ph-e, phi<PHI AE) RA1E
min. 0.10
Ï
max. 200.00
©©©©
1627 RA2E
Fault det. resistance (ph-e, phi>PHI AE) RA2E
min. 0.10
Ï
max. 200.00
©©©©
1628 ANGLE PHIA
Fault det. ph-ph angle betw. RA1/RA2 PHI A
min. 30
Ý
max. 80
©©©©