Reference Table for Functional Parameters 7SA511
²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²
1000 PARAMETERS
©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©
1100 POWERSYSTEM DATA
1101 CT STARPNT
Current transformer polarity
TOWARDS LINE
[ ] Towards line
TOWARDS BUSBAR
[ ] Towards busbar
1102 SYSTEMSTAR
System star-point condition
SOLIDLY EARTHED [ ] Solidly earthed
COMPENSATED
[ ] Compensated
ISOLATED
[ ] Isolated
1103 Un PRIMARY
Primary rated voltage
min. 1
kV
max. 1200
©©©©
1104 Un SECOND.
Secondary rated voltage
min. 80
V
max. 125
©©©©
1105 In PRIMARY
Primary rated current
min. 10
A
max. 5000
©©©©
1109 Ux CONNECT
Ux voltage transformer connection
NOT CONNECTED
[ ] Not connected
Udelta TRANSFORM [ ] Udelta transformer
U2 TRANSFORMER
[ ] U2 transformer
1110 Uph/Udelta
Matching factor Uph/Udelta (sec.earth voltage)
min. 0.10
max. 9.99
©©©©
1111 Ie CT
Ie current transformer
PROTECTED LINE
[ ] Protected line
PARALLEL LINE
[ ] Parallel line
1112 Ie/Iph
Matching factor Ie/Iph for earth current
min. 0.100
max. 20.000
©©©©
1116 U2 CONNECT
Voltage transformer U2 input connection
L1-L2
[ ] L1-L2
L2-L3
[ ] L2-L3
L3-L1
[ ] L3-L1
L1-E
[ ] L1-E
L2-E
[ ] L2-E
L3-E
[ ] L3-E
1117 RE/RL
Residual compensating factor RE/RL
min. -7.00
max. 7.00
©©©©
1118 XE/XL
Residual compensating factor XE/XL
min. -7.00
max. 7.00
©©©©