
Functions
2.1 General
SIPROTEC, 7RW80, Manual
C53000-G1140-C233-1, Release date 10.2010
36
2.1.4.3
Settings
2.1.4.4
Information List
2.1.5
Settings Groups
Up to four different setting groups can be created for establishing the device's function settings.
2.1.5.1
Description
Changing Setting Groups
During operation the user can switch back and forth setting groups locally, via the operator panel, binary inputs
(if so configured), the service interface using a personal computer, or via the system interface. For reasons of
safety it is not possible to change between setting groups during a power system fault.
A setting group includes the setting values for all functions that have been selected as
Enabled
during con-
figuration (see Section 2.1.1.2). In 7RW80 relays, four independent setting groups (A to D) are available. While
setting values may vary, the selected functions of each setting group remain the same.
Addr.
Parameter
Setting Options
Default Setting
Comments
401
WAVEFORMTRIGGE
R
Save w. Pickup
Save w. TRIP
Start w. TRIP
Save w. Pickup
Waveform Capture
402
WAVEFORM DATA
Fault event
Pow.Sys.Flt.
Fault event
Scope of Waveform Data
403
MAX. LENGTH
0.30 .. 5.00 sec
2.00 sec
Max. length of a Waveform
Capture Record
404
PRE. TRIG. TIME
0.05 .. 0.50 sec
0.10 sec
Captured Waveform Prior to
Trigger
405
POST REC. TIME
0.05 .. 0.50 sec
0.10 sec
Captured Waveform after Event
406
BinIn CAPT.TIME
0.10 .. 5.00 sec;
∞
0.50 sec
Capture Time via Binary Input
No.
Information
Type of In-
formation
Comments
-
FltRecSta
IntSP
Fault Recording Start
4
>Trig.Wave.Cap.
SP
>Trigger Waveform Capture
203
Wave. deleted
OUT_Ev
Waveform data deleted
30053
Fault rec. run.
OUT
Fault recording is running