Functions
2.1 General
SIPROTEC, 6MU805, Manual
C53000-G1140-C380-5, Release date 06.2018
29
2.1.3.2
Setting Notes
Configuration
Fault recording (waveform capture) will only take place if address
0104
OSC. FAULT REC.
is set to
Enabled
.
Other settings pertaining to fault recording (waveform capture) are found in the OSC. FAULT REC. submenu
of the SETTINGS menu.
The actual storage time begins at the pre-fault time
PRE. TRIG. TIME
(address
404
) ahead of the reference
instant, and ends at the post-fault time
POST REC. TIME
(address 0
405
) after the storage criterion has reset.
The maximum storage time for each fault recording (
MAX. LENGTH
) is entered in address
0403
. Recording
per event must not exceed 6 seconds. A total of 8 records can be saved. However, the total length of time of
all fault records in the buffer must not exceed 18 seconds.
An oscillographic record can be triggered by a status change of a binary input, or from a PC via the operator
interface. Storage is then triggered dynamically. The length of the fault recording is set in address
0406
BinIn
CAPT.TIME
but not longer than
MAX. LENGTH
(address
0403
). Pre-fault and post-fault times will add to this.
If the binary input time is set to
, the length of the record equals the time that the binary input is activated
(static), but not longer than the
MAX. LENGTH
(address
0403
).
2.1.3.3
Settings
2.1.3.4
Information List
2.1.4
Power System Data 2
2.1.4.1
Description
The general data (
P.System Data 2
) include parameters common to all functions, i.e. not associated with a spe-
cific monitoring function. In contrast to the
P.System Data 1
before, they can be changed with the parameter
group.
Addr.
Parameter
Setting Options
Default Setting
Comments
0403
MAX. LENGTH
0.30 .. 6.00 sec
2.00 sec
Max. length of a Waveform
Capture Record
0404
PRE. TRIG. TIME
0.05 .. 0.50 sec
0.25 sec
Captured Waveform Prior to
Trigger
0405
POST REC. TIME
0.05 .. 0.50 sec
0.10 sec
Captured Waveform after Event
0406
BinIn CAPT.TIME
0.10 .. 5.00 sec;
0.50 sec
Capture Time via Binary Input
No.
Information
Type of Information
Comments
-
FltRecSta
IntSP
Fault Recording Start
4
>Trig.Wave.Cap.
SP
>Trigger Waveform Capture
203
Wave. deleted
OUT_Ev
Waveform data deleted
30053
Fault rec. run.
OUT
Fault recording is running