2.2 Command processing
19
6MD665 Manual
C53000-G1876-C103-3
2.2.2.2
Information
2.2.3
Control Authorization
For the control of switchgear there are several types of commands that have to be con-
sidered.
Usecases
Operation of circuit breakers, disconnectors and ground electrodes
Raising and lowering transformer LTCs
Control of Petersen coils
Manually overriding/updating information of process-dependent objects
Establishing internal settings
Setting and resetting internal buffers or data stocks
Adding/removing additional information
Requirements
For more information see SIPROTEC
®
system description
2.2.3.1
Description
Commands to the system
These are all commands that are directly output to the switchgear to change their
process state:
• Switching commands for the control of circuit breakers (unsynchronised), discon-
nectors and ground electrodes,
• Step commands, e.g. raising and lowering transformer LTCs
• Setpoint commands with configurable time settings, e.g. to control Petersen coils
No.
Message
Type of Information
Description
-
Q0
BR_D2
circuit breaker Q0
-
Q0
DM
circuit breaker Q0
-
Q1
BR_D2
bus disconnector Q1
-
Q1
DM
bus disconnector Q1
-
Q2
BR_D2
bus disconnector Q2
-
Q2
DM
bus disconnector Q2
-
Q8
BR_D2
earthing isolator Q8
-
Q8
DM
earthing isolator Q8
-
Q9
BR_D2
feeder disconnector Q9
-
Q9
DM
feeder disconnector Q9
-
ReleaseQ0
IE
Release circuit breaker Q0
-
ReleaseQ1
IE
Release bus disconnector Q1
-
ReleaseQ2
IE
Release bus disconnector Q2
-
ReleaseQ8
IE
Release earthing isolator Q8
-
ReleaseQ9
IE
Release feeder disconnector Q9
Summary of Contents for SIPROTEC 6MD665
Page 8: ...Preface vi 6MD665 Manual C53000 G1876 C103 3 ...
Page 14: ...Contents vi 6MD665 Manual C53000 G1876 C103 3 ...
Page 140: ...3 Installation and Commissioning 126 6MD665 Manual C53000 G1876 C103 3 ...
Page 166: ...4 Technical Data 152 6MD665 Manual C53000 G1876 C103 3 ...
Page 210: ...Literature 196 6MD665 Manual C53000 G1876 C103 3 ...
Page 222: ...Index 208 6MD665 Manual C53000 G1876 C103 3 ...