2 Functions
14
6MD665 Manual
C53000-G1876-C103-3
Value (fleeting): ON
“SynchClock”
Acknowledgement of a clock synchronisation.
Value (fleeting): ON
“Clock SyncError”
Indication: Clock synchronisation error.
Value: ON, the synchronizing event is missing after the parametrized tolerance time.
Value: OFF, a synchronizing event has again arrived.
“DayLightSavTime”
Indication: Daylight saving time switchover.
Value: ON, a time synchronisation job with summertime was detected by the date-
clocktime processing.
Value: OFF, a time synchronisation job without daylight saving time was detected.
“Settings Calc.”
Annunciation that a parametrization is current.
Value: ON, the function is reserved for parametrization.
Value: OFF, the function has been enabled again.
“Settings Check”
Message that the device operates with new parameters which are not yet saved (on-
line parameterization).
Value: ON, the test has begun.
Value: OFF, the test is ended, i.e. the device is either operative again, or the new
parameters have been saved permanently, or no parameter check is current.
“Level-2 change”
The indication is issued as ON, as soon as the parameter set loaded via DIGSI
®
was
changed by an online parametrisation and the device operates with these new param-
eters. The indication is OFF as long as the parameter set loaded via DIGSI
®
is not
changed or is again issued as OFF, if a parameter set was completely newly loaded
and the unit operates with these parameters. The information value of the message
(ON/OFF) is preserved during an initial and a resume.
Value: ON, parameter changes online at the unit or via parametrisation command.
Value: OFF, parameter set completely reloaded.
“Local change”
Indication that the local operation setting was cancelled.
This message is reserved for DIGSI
®
.
“Error Board 1”
Indication: The BG1 module either does not exist or is defective.
Value: ON
“Event Lost”
Fleeting indication Indication lost
“Error FMS1”
Fault in the PROFIBUS FMS connection, fibre optic cable 1 with double ring connec-
tion
Summary of Contents for SIPROTEC 6MD665
Page 8: ...Preface vi 6MD665 Manual C53000 G1876 C103 3 ...
Page 14: ...Contents vi 6MD665 Manual C53000 G1876 C103 3 ...
Page 140: ...3 Installation and Commissioning 126 6MD665 Manual C53000 G1876 C103 3 ...
Page 166: ...4 Technical Data 152 6MD665 Manual C53000 G1876 C103 3 ...
Page 210: ...Literature 196 6MD665 Manual C53000 G1876 C103 3 ...
Page 222: ...Index 208 6MD665 Manual C53000 G1876 C103 3 ...