2.1 General functions
13
6MD665 Manual
C53000-G1876-C103-3
Value: ON
“Reset LED”
Tagging command for acknowledging the LEDs of SICAM or DIGSI
®
.
Value: ON
“>Light on”
Display on/off via binary input.
Value: ON/OFF
“Chatter ON”
Central chatter suppression message.
This message indicates if the chatter suppression responded during a binary message
subject to the chatter processing.
Value: ON, the chatter suppression responded for at least one object.
Value: OFF, chatter suppression did not respond for any objects.
“Error PwrSupply”
Indication: The power supply unit is faulty.
Value: ON
“Fail Battery”
Indication: The battery is faulty.
Value: ON
“DataStop”
Data transmission blockage for indications, metered and measured values.
With data transmission blockage on, all information in the monitoring direction is
marked with the transmission blockage bit. The actual transmission blockage is per-
formed in the control center.
Value: ON/OFF
“>DataStop”
Predefined binary input for tagging
´'DWD6WRSµ
Value: ON/OFF
“Test mode”
This operating mode is used for device tests during commissioning or maintenance.
In test mode, all information in monitoring direction is marked with UBF test bit. This
procedure serves to avoid that events caused by the test mode initiate unwanted reac-
tions (horn, derived commands and indications, etc.) in higher-level system compo-
nents (DIGSI
®
or SICAM). This operating mode can be activated and deactivated by
a tagging command in DIGSI
®
.
Value: ON/OFF
“HWTestMod”
Hardware test mode: DIGSI
®
switches ON this operating mode if the user activates
the functions Set binary input, Set output relay, Set messages, for example, in start-
up mode. DIGSI
®
switches OFF the hardware test mode when leaving the start-up
area. After the switch-off command, the "Hardware test mode OFF" message is output
and an initial device start-up is initiated after a period of 5 seconds.
Value: ON/OFF
“>Time Synch”
Input for the external minute pulse.
Summary of Contents for SIPROTEC 6MD665
Page 8: ...Preface vi 6MD665 Manual C53000 G1876 C103 3 ...
Page 14: ...Contents vi 6MD665 Manual C53000 G1876 C103 3 ...
Page 140: ...3 Installation and Commissioning 126 6MD665 Manual C53000 G1876 C103 3 ...
Page 166: ...4 Technical Data 152 6MD665 Manual C53000 G1876 C103 3 ...
Page 210: ...Literature 196 6MD665 Manual C53000 G1876 C103 3 ...
Page 222: ...Index 208 6MD665 Manual C53000 G1876 C103 3 ...