Inrush Restraint
Controlled Elements
Time Overcurrent Elements
50-1, 50N-1, 51, 51N, 67-1, 67N-1
Setting Ranges / Increments
Stabilization factor
Ι
2f
/
Ι
10 % to 45 %
Increments 1 %
Functional Limits
Lower Function Limit Phases
for
Ι
Nom
= 1 A
at least one phase current (50 Hz and 100 Hz) ≥ 25 mA
for
Ι
Nom
= 5 A
at least one phase current (50 Hz and 100 Hz) ≥ 125 mA
Lower Function Limit ground
for
Ι
Nom
= 1 A
Ground current (50 Hz and 100 Hz) ≥ 25 mA
for
Ι
Nom
= 5 A
Ground current (50 Hz and 100 Hz) ≥ 125 mA
Upper Function Limit,
configurable
for
Ι
Nom
= 1 A
0.30 A bis 25.00 A
increments 0.01 A
for
Ι
Nom
= 5 A
1.50 A bis 125.00 A
increments 0.01 A
Crossblock
Crossblock
Ι
A
,
Ι
B
,
Ι
C
ON/OFF
4.5
Technical Data
4.5 Inrush Restraint
464
SIPROTEC 4, 7SJ62/64, Manual
C53000-G1140-C207-8, Edition 08.2016