Permissible temporary operating temperature
(tested for 96 h)
–20 °C to +70 °C or –4 °F to +158 °F
(legibility of the display may be restricted from +55 °C
or +131 °F
Recommended for permanent operation (according
to IEC 60255-6)
–5 °C to +55 °C or +23 °F to +131 °F
Limiting Temperatures for Storage
–25 °C to +55 °C or –13 °F to +131 °F
Limiting temperatures for transport
–25 °C to +70 °C or –13 °F to +158 °F
STORE AND TRANSPORT THE DEVICE WITH FACTORY PACKAGING!
1
) UL–certified according to Standard 508 (Industrial Control Equipment):
Limiting temperatures for normal operation (i.e.
output relays not energized)
–20 °C to +70 °C or –4 °F to +158 °F
Limiting temperatures with maximum load (max.
cont. permissible energization of inputs and
outputs)
–5 °C to +55 °C or +23 °F to +131 °F für 7SJ62
–5 °C to +40 °C or +23 °F to +104 °F für 7SJ64
Humidity
Permissible humidity
Mean value per year ≤ 75 % relative humidity;
on 56 days of the year up to 93 % relative humidity;
condensation must be avoided!
Siemens recommends that all devices be installed such that they are not exposed to direct sunlight, nor
subject to large fluctuations in temperature that may cause condensation to occur.
Service Conditions
The protective device is designed for use in an industrial environment and an electrical utility environment.
Proper installation procedures should be followed to ensure electromagnetic compatibility (EMC).
In addition, the following is recommended:
•
All contacts and relays that operate in the same cubicle, cabinet, or relay panel as the numerical protec-
tive device should, as a rule, be equipped with suitable surge suppression components.
•
For substations with operating voltages of 100 kV and above, all external cables should be shielded with
a conductive shield grounded at both ends. For substations with lower operating voltages, no special
measures are normally required.
•
Do not withdraw or insert individual modules or boards while the protective device is energized. In with-
drawn condition, some components are electrostatically endangered; during handling the ESD stand-
ards (for Electrostatic Sensitive Devices) must be observed. They are not endangered when inserted into
the case.
Certifications
UL listing
UL recognition
7SJ62**-*B***-****
Models with threaded
terminals
7SJ62**-*D***-****
Types with plug-in
terminals
7SJ62**-*E***-****
7SJ64**-*B***-****
7SJ64**-*A***-****
7SJ64**-*C***-****
7SJ64**-*D***-****
7SJ64**-*E***-****
7SJ64**-*G***-****
7SJ64**-*F***-****
Constructive Designs
Case
7XP20
4.1.8
4.1.9
4.1.10
Technical Data
4.1 General Device Data
448
SIPROTEC 4, 7SJ62/64, Manual
C53000-G1140-C207-8, Edition 08.2016
Summary of Contents for SIPROTEC 4
Page 8: ...8 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 18: ...18 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 30: ...30 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 540: ...540 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 594: ...594 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 720: ...720 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...