![Siemens SIPROTEC 4 User Manual Download Page 439](http://html.mh-extra.com/html/siemens/siprotec-4/siprotec-4_user-manual_382653439.webp)
7SJ640
Approx. 5 W
Approx. 9 W
7SJ641
Approx. 5,5 W
Approx. 13 W
7SJ642
Approx. 5,5 W
Approx. 12 W
7SJ645
Approx. 6,5 W
Approx. 15 W
7SJ647
Approx. 7,5 W
Approx. 21 W
Bridging time for failure/short-circuit, IEC 60255-
11 (in not energized operation)
≥ 50 ms at V ≥ DC 110 V
≥ 20 ms at V ≥ DC 24 V
Alternating Voltage
Voltage Supply via Integrated Converter
Rated auxiliary voltage AC V
Aux
AC 115 V
AC 230 V
Permissible Voltage Ranges
AC 92 V to 132 V
AC 184 V to 265 V
Power input (at AC 115 V/ 230 V)
Quiescent
Energized
7SJ62
Approx. 3 VA
Approx. 9 VA
7SJ640
Approx. 7 VA
Approx. 12 VA
7SJ641
Approx. 9 VA
Approx. 19,5 VA
7SJ642
Approx. 9 VA
Approx. 18,5 VA
7SJ645
Approx. 12 VA
Approx. 23 VA
7SJ647
Approx. 16 VA
Approx. 33 VA
Bridging Time for Failure/Short-Circuit
(in not energized operation)
200 ms
Binary Inputs and Outputs
Binary Inputs
Variant
Number
7SJ621*-
8 (configurable)
7SJ622*-
11 (configurable)
7SJ623*-
8 (configurable)
7SJ624*-
11 (configurable)
7SJ625*-
8 (configurable)
7SJ626*-
11 (configurable)
7SJ640*-
7 (configurable)
7SJ641*-
15 (configurable)
7SJ642*-
20 (configurable)
7SJ645*-
33 (configurable)
7SJ647*-
48 (configurable)
Rated voltage range
DC 24 V to 250 V, bipolar
7SJ62
– – –
BI1 ... BI11
7SJ640
– – –
BI1 ... 7
7SJ641
– – –
BI1 ... 15
7SJ642
BI8... 19
BI1 ... 7; BI20
7SJ645
BI8... 19; BI21...32
BI1...7; BI20; BI33
7SJ647
BI8... 19; BI21...32
BI1...7; BI20; BI33...48
Current consumption, picked up
(independent of the operating voltage)
approx. 0,9 mA
approx. 1.8 mA
4.1.3
Technical Data
4.1 General Device Data
SIPROTEC 4, 7SJ62/64, Manual
439
C53000-G1140-C207-8, Edition 08.2016
Summary of Contents for SIPROTEC 4
Page 8: ...8 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 18: ...18 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 30: ...30 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 540: ...540 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 594: ...594 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 720: ...720 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...