[polaritaetspruefung-ie-mituen-gemessen, 1, en_US]
Figure 3-39
Polarity testing for
Ι
N
, example with current transformers configured in a Holmgreen-connec-
tion (VTs with broken delta connection -- e-n winding)
[polaritaetspruefung-ie-mituen-berechnet-211002-kn, 1, en_US]
Figure 3-40
Polarity testing for
Ι
N
, example with current transformers configured in a Holmgreen-connec-
tion (VTs Wye-connected)
Checking the Temperature Detection
After the termination of the RS485 port and the setting of the bus address have been verified according to
Section
, the measured temperature values and thresholds can be checked.
3.3.13
Mounting and Commissioning
3.3 Commissioning
SIPROTEC 4, 7SJ62/64, Manual
431
C53000-G1140-C207-8, Edition 08.2016