Addr.
Parameter
Setting Options
Default Setting
Comments
5411
81-3 DELAY
0.00 .. 100.00 sec; ∞
3.00 sec
81-3 Time delay
5412
81-4 PICKUP
40.00 .. 60.00 Hz
51.00 Hz
81-4 Pickup
5413
81-4 PICKUP
50.00 .. 70.00 Hz
61.00 Hz
81-4 Pickup
5414
81-4 DELAY
0.00 .. 100.00 sec; ∞
30.00 sec
81-4 Time delay
5415A
DO differential
0.02 .. 1.00 Hz
0.02 Hz
Dropout differential
5421
FCT 81-1 O/U
OFF
ON f>
ON f<
OFF
81-1 Over/Under Frequency
Protection
5422
FCT 81-2 O/U
OFF
ON f>
ON f<
OFF
81-2 Over/Under Frequency
Protection
5423
FCT 81-3 O/U
OFF
ON f>
ON f<
OFF
81-3 Over/Under Frequency
Protection
5424
FCT 81-4 O/U
OFF
ON f>
ON f<
OFF
81-4 Over/Under Frequency
Protection
Information List
No.
Information
Type of
Informa-
tion
Comments
5203
>BLOCK 81O/U
SP
>BLOCK 81O/U
5206
>BLOCK 81-1
SP
>BLOCK 81-1
5207
>BLOCK 81-2
SP
>BLOCK 81-2
5208
>BLOCK 81-3
SP
>BLOCK 81-3
5209
>BLOCK 81-4
SP
>BLOCK 81-4
5211
81 OFF
OUT
81 OFF
5212
81 BLOCKED
OUT
81 BLOCKED
5213
81 ACTIVE
OUT
81 ACTIVE
5214
81 Under V Blk
OUT
81 Under Voltage Block
5232
81-1 picked up
OUT
81-1 picked up
5233
81-2 picked up
OUT
81-2 picked up
5234
81-3 picked up
OUT
81-3 picked up
5235
81-4 picked up
OUT
81-4 picked up
5236
81-1 TRIP
OUT
81-1 TRIP
5237
81-2 TRIP
OUT
81-2 TRIP
5238
81-3 TRIP
OUT
81-3 TRIP
5239
81-4 TRIP
OUT
81-4 TRIP
2.9.4
Functions
2.9 Frequency Protection 81 O/U
166
SIPROTEC 4, 7SJ62/64, Manual
C53000-G1140-C207-8, Edition 08.2016
Summary of Contents for SIPROTEC 4
Page 8: ...8 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 18: ...18 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 30: ...30 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 540: ...540 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 594: ...594 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 720: ...720 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...