By reading the operational measured values one should check that within the framework of the measuring
tolerances
•
Both voltages U1 and U2 are equal
•
Both frequencies f1 and f2 are equal.
If the secondary voltages are not equal due to different voltage transformer, an appropriate correction can be
performed with the help of the adaptation factor 6121
Balancing U1/U2
.
In the operational measured values of the 7VE61 and 7VE63 one should check also that within the framework
of the measuring tolerances
•
The difference voltage dU is zero
•
The difference frequency df is zero
•
The difference angle dα is zero.
If for three-phase systems from the 7VE61 and 7VE63 the phase rotation checks are executed, the same phase
rotation has to be displayed for both voltages in the operational measured values.
With multiple busbars, the attempt for each busbar voltage has to be checked.
In case of several synchronizing points, each of the synchronizing points has to be tested.
[ueberpruefung-messspg-im-messfeld-beispiel1-280203-oz, 1, en_GB]
Figure 3-21
Testing the measuring voltages in the measuring field — Example 1
Synchronization of Networks
The previous rules apply for the synchronization of systems. The following figure shows a possible switching
arrangement. Identical tests are executed as for the “checking with busbar voltage transformer”. For details,
see above.
Mounting and Commissioning
3.3 Commissioning
SIPROTEC 4, 7VE61 and 7VE63, Manual
179
C53000-G1176-C163-3, Edition 10.2017
Summary of Contents for SIPROTEC 4 7VE61
Page 8: ...8 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 24: ...24 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 142: ...142 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 192: ...192 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 222: ...222 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 230: ...230 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 256: ...256 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 314: ...314 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 316: ...316 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 330: ...330 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...