![Siemens SIPLUS HCS3200 Operating Instructions Manual Download Page 35](http://html.mh-extra.com/html/siemens/siplus-hcs3200/siplus-hcs3200_operating-instructions-manual_376934035.webp)
SIPLUS HCS3200
Operating Instructions, 07/2014, A5E31278506C/002
35
Commissioning
7
7.1
Requirements
7.1.1
Hardware requirements
Requirements for commissioning
Before commissioning starts, the system components must be installed and wired up.
The following is necessary:
●
SIMATIC S7 CPU / SIMOTION with PROFIBUS DP interface
●
PROFIBUS DP
●
SIPLUS HCS3200 heating controller
7.1.2
Integrating the GSD file
You will need the language-specific GSD file "SIEM81A4.GSx" for PROFIBUS configuration.
For this purpose, the GSD file must be installed in the configuration software.
You can download the GSD file from the Siemens Service&Support website
http://www.siemens.com/automation/service&support
Procedure
If this GSD file is not yet available in your configuration software version, integrate the GSD
file in STEP 7 V5.x or in STEP 7 V11 and higher (TIA Portal) in accordance with the online
help for STEP 7.
If a non-Siemens DP master is used, install the GSD file as described in the manufacturer's
instructions.
Quantity structure of the
DP slave
●
10 bytes output data
●
3 words input data
●
21 bytes of diagnostic data
●
Baud rates up to 12 Mbaud
●
Supported standard: PROFIBUS DP
Summary of Contents for SIPLUS HCS3200
Page 1: ......
Page 2: ......
Page 24: ...Mounting 5 3 Final work SIPLUS HCS3200 24 Operating Instructions 07 2014 A5E31278506C 002 ...
Page 74: ......