Parameter assignment/Addressing
10.2 Description of parameters
SIPART PS2 with PROFIBUS communication
156
Operating Instructions, 09/2007, A5E00127926-07
10.2.2.18
Description of parameter 48
48.XDIAG - activation of advanced diagnostics
Advanced diagnostics is deactivated by default. The "48.XDIAG" parameter is thus set to
"OFF". Three operating modes are available to activate advanced diagnostics:
●
On1: advanced diagnostics is activated and the threshold 3 fault messages are triggered
through the fault message output.
●
On2: advanced diagnostics is activated. The threshold 2 fault messages are triggered
through alarm output 2 and the threshold 3 fault messages are additionally triggered
through the fault message output.
●
On3: advanced diagnostics is activated. The threshold 1 fault messages are triggered
through alarm output 1, the threshold 2 fault messages through alarm output 2 and the
threshold 3 fault messages are additionally triggered through the fault message output.
Note
Note that you have to select one of the operating modes from "On1" to "On3" to enable
the menu items of advanced diagnostics from "A. PST" to "P. PAVG" in the digital
display.
The factory setting is "OFF", which deactivates the parameters of menu items A to P by
default. The corresponding parameters are displayed only after you activate the
corresponding menu item with "On".
In advanced diagnostics, the threshold of the fault message is displayed using columns in
addition to the error code. These columns are shown on the digital display as follows:
Figure 10-2 Display of a threshold 1 fault message
Figure 10-3 Display of a threshold 2 fault message