Connection Elements and Conductor Cross-Sections
i
i
NOTE
Observe the manufacturer specifications when using a bootlace ferrule.
Mechanical Requirements
The fasteners and their associated components are designed for the following mechanical requirements:
Permissible tightening torque at clamping screw
0.7 Nm
Installation and Removal
²
Switch off the device before starting work.
Assembly tool
²
Use a screwdriver (DIN 4 x 0.8).
Removal
²
Use a screwdriver to carefully bend the left and right spring clips outwards.
²
Carefully pull out the terminal block.
²
Seal the contacts with a cover cap (see
Installation
²
Pull the cover cap off the terminal.
²
Carefully insert the terminal block into the spring clips.
²
Both spring clips must engage clearly audibly.
5.3.4
Working on the Device
5.3 Installing Current and Voltage Terminals
SIPROTEC 5 Compact, Hardware Description, Manual
51
C53000-G5300-C002-3, Edition 12.2021
Summary of Contents for SIP5C
Page 8: ...8 SIPROTEC 5 Compact Hardware Description Manual C53000 G5300 C002 3 Edition 12 2021 ...
Page 16: ...16 SIPROTEC 5 Compact Hardware Description Manual C53000 G5300 C002 3 Edition 12 2021 ...
Page 38: ...38 SIPROTEC 5 Compact Hardware Description Manual C53000 G5300 C002 3 Edition 12 2021 ...
Page 52: ...52 SIPROTEC 5 Compact Hardware Description Manual C53000 G5300 C002 3 Edition 12 2021 ...
Page 66: ...66 SIPROTEC 5 Compact Hardware Description Manual C53000 G5300 C002 3 Edition 12 2021 ...
Page 70: ...70 SIPROTEC 5 Compact Hardware Description Manual C53000 G5300 C002 3 Edition 12 2021 ...
Page 72: ...72 SIPROTEC 5 Compact Hardware Description Manual C53000 G5300 C002 3 Edition 12 2021 ...
Page 74: ...74 SIPROTEC 5 Compact Hardware Description Manual C53000 G5300 C002 3 Edition 12 2021 ...