First Steps
Electrical Inspection
Device Protection
!
DANGER
Danger when connecting the SIPROTEC 5 Compact device
Noncompliance with the safety notes will result in death, severe injury, or considerable material
damage.
²
The device must be situated in the operating area for at least 2 hours before you connect it to the
power supply for the first time. This prevents condensed water from forming in the device.
²
If the device has been in storage for more than 2 years, connect it to an auxiliary voltage for 1 to
2 days. This will cause the electrolytic capacitors to form on the printed circuit board assemblies again.
²
Perform the electrical inspection.
Activating the Battery
i
i
NOTE
The battery is covered by a protective film, which also prevents premature discharge.
The battery compartment is on the underside of the device. Take the battery out of the battery compart-
ment to remove the protective film. Do not pull the insulating film out when the battery slide is closed, as
this may damage the contacts in the battery holder.
i
i
NOTE
Use only insulated tools to open and close the battery cover and to remove and insert the battery.
Activate the battery for SIPROTEC 5 Compact devices as follows:
²
Open the battery compartment on the bottom of the device.
²
Fix the insulated tool in the film tab area. Push the battery out using the tool.
²
Remove the protective film.
²
Reinsert the battery.
²
Close the battery compartment on the bottom of the device.
Grounding a Device
All SIPROTEC 5 Compact devices, are protection class I equipment and must be connected to the system
ground prior to commissioning.
²
Ground each module with solid low-impedance system grounding (cross-section ≥ 4.0 mm
2
(≥ 0.0062
in
2
), grounding area ≥ M4, torque: at least 1.2 Nm).
²
In order to ensure the electromagnetic compatibility (EMC) of the device, connect the protective
grounding terminals of the modules to each other in series connection. Use the double protective
grounding terminals of the individual modules for this purpose.
²
Connect the protective conductor of the protection device (connected modules) to the protective
grounding terminal of the installation (for example control cabinet) with a single connection to the base
module of the protection device.
5.1
5.1.1
Working on the Device
5.1 First Steps
40
SIPROTEC 5 Compact, Hardware Description, Manual
C53000-G5300-C002-3, Edition 12.2021
Summary of Contents for SIP5C
Page 8: ...8 SIPROTEC 5 Compact Hardware Description Manual C53000 G5300 C002 3 Edition 12 2021 ...
Page 16: ...16 SIPROTEC 5 Compact Hardware Description Manual C53000 G5300 C002 3 Edition 12 2021 ...
Page 38: ...38 SIPROTEC 5 Compact Hardware Description Manual C53000 G5300 C002 3 Edition 12 2021 ...
Page 52: ...52 SIPROTEC 5 Compact Hardware Description Manual C53000 G5300 C002 3 Edition 12 2021 ...
Page 66: ...66 SIPROTEC 5 Compact Hardware Description Manual C53000 G5300 C002 3 Edition 12 2021 ...
Page 70: ...70 SIPROTEC 5 Compact Hardware Description Manual C53000 G5300 C002 3 Edition 12 2021 ...
Page 72: ...72 SIPROTEC 5 Compact Hardware Description Manual C53000 G5300 C002 3 Edition 12 2021 ...
Page 74: ...74 SIPROTEC 5 Compact Hardware Description Manual C53000 G5300 C002 3 Edition 12 2021 ...