Description
9229 0025 176 0E
35
2021-11-15
SION
®
vacuum circuit-breaker for generator switching applications
Fig. 42
Technical specifications, SION
®
generator circuit-breaker
Dimensions and weights
The dimensions of the vacuum circuit-breaker can be taken from the relevant dimen-
sional drawing. If needed, they can be obtained from your Siemens representative.
The weight is indicated on the vacuum circuit-breaker name plate (see Fig. 40), or
refer to the associated dimension drawing.
Rated voltage
U
r
(at
f
r
50/60 Hz)
kV
12
17.5
d)
Rated normal current
I
r
A
1250 – 3150 / 4000
fc
c)
Rated lightning impulse withstand voltage (peak value)
U
p
kV
75 (95
a)
)
95
d)
Rated short-duration power frequency withstand voltage (RMS)
U
d
kV
28 (42
a)
)
38
d)
Rated short-circuit breaking current
I
sc
kA
31.5
DC component of the rated short-circuit breaking current
I
sc
kA
65
Rated short-circuit breaking current
I
ma
kA
87
Pole-centre distance
mm
210, 275
Distance between lower and upper terminal
mm
275, 310
Standard rated operating sequence
CO – 30 min – CO
Classification for circuit breakers G1 or G2 as per IEC/IEEE
62271-37-013:2015
G1
G2
Generator side rated short-circuit breaking current
I
scg
kA
25
18.5
DC component of the rated short-circuit breaking current
I
sc
%
110
130
Asymmetrical breaking current
kA
46
39
a)
On request
c
only with additional active cooling (fc)
d)
Rated insulation level as per IEC 62271-100:2017