![Siemens SION 3AE5 Operating Instructions Manual Download Page 62](http://html.mh-extra.com/html/siemens/sion-3ae5/sion-3ae5_operating-instructions-manual_1265260062.webp)
Maintenance
62
9229 0025 176 0A
2019-08-05
The insulating parts must be clean if their dielectric strength is to be guaranteed.
Rub insulating parts with a moist cloth.
As a cleaning agent, use only warm water with a mild, liquid household cleaner add-
ed and leave to dry.
For joints and bearing points that cannot be disassembled, only wipe off with a dry,
lint-free cloth.
Under no circumstances may these joints and bearing points be cleaned with clean-
ing agents or water!
Service life of the vacuum interrupters
If switching operations occur frequently under overload or short circuit, the service
life of the vacuum interrupters may be reached prematurely.
Accessories and spare parts
Replacing spare parts
To ensure that the device operates reliably, spare parts are permitted to be replaced
only by personnel trained and certified by Siemens.
The vacuum circuit-breaker should be taken out of the switchgear or switch cabinet
for servicing.
Fig. 95
Accessories available for order
Always specify the vacuum circuit-breaker's type and serial no. (see “Name plate”
on page 31) when ordering spare parts.
CAUTION
Risk of injury due to unexpected switching operation
Switching operations are still possible when low voltage is connected.
• There must be no remote access.
• Disconnect vacuum circuit-breaker from the control supply voltage or switch
off.
• Alternatively: Disconnect the low-voltage plug or terminal connection.
Accessory/spare part
Order number
Comment
Operating instructions
9229 0025 100
Unpacking instructions
9229 0027 100
Hand crank
3AX1530-4B
Handle on withdrawable part
3AX1430-2C
Molykote Longterm 2
3AX1133-4L
Vaseline (contact grease SN10611)
e.g. Atlantic white, Atlantic Mineralöl-
werk GmbH
3AX1133-4A
Pasty consistency, ignition point 210 °C, low acid