NOTICE
•
OFF3 can be entered using a wide range of command sources via BICO parameters
P0848 (BI: 1. OFF3) and P0849 (BI: 2. OFF3).
•
OFF3 is active low.
•
When simultaneously selecting the various OFF commands, the following priority
applies: OFF2 (highest priority) – OFF3 – OFF1
5.6.2.2
Running the inverter in JOG mode
Functionality
The JOG function can be controlled by either the (built-in) BOP or the digital inputs. When
controlled by the BOP, pressing the RUN button will cause the motor to start and rotate at
the pre-set JOG frequency (P1058). The motor stops when the RUN button is released.
When using the digital inputs as the JOG command source, the JOG frequency is set by
P1058 for JOG right and P1059 for JOG left.
The JOG function allows:
●
to check the functionality of the motor and inverter after commissioning has been
completed (first traversing motion, checking the direction of rotation, etc.)
●
to bring a motor or a motor load into a specific position
●
to traverse a motor, e.g. after a program has been interrupted