Parameter list
7.2 Parameter list
SINAMICS V20 Inverter
Operating Instructions, 07/2012, A5E03728167
163
Parameter
Function
Range
Factory
default
Can be
changed
Scaling
Data
set
Data
type
Acc.
Level
P1042[0...2] CI: MOP auto setpoint
-
0
T
-
CDS
U32 /
I32
3
Sets the signal source for the setpoint of the motorized potentiometer if automatic mode P1041 is selected.
Notice:
Refer to: P1041
P1043[0...2] BI: MOP accept
rampgenerator setpoint
-
0
T
-
CDS
U32 /
Bin
3
Sets the signal source for the setting command to accept the setting value for the motorized potentiometer.
The value becomes effective for a 0 / 1 edge of the setting command.
Notice:
Refer to: P1044
P1044[0...2] CI: MOP rampgenerator
setpoint
-
0
T
-
CDS
U32 /
I32
3
Sets the signal source for the setpoint value for the MOP. The value becomes effective for a 0 / 1 edge of
the setting command.
Notice:
Refer to: P1043
r1045
CO: MOP input
frequency of the RFG
[Hz]
-
-
-
-
-
Float 3
Displays the motorized potentiometer setpoint before it passed the MOP RFG.
P1047[0...2] MOP ramp-up time of
the RFG [s]
0.00 -
1000.00
10.00
U, T
-
DDS
Float 2
Sets the ramp-up time for the internal MOP ramp-function generator. The setpoint is changed from zero up
to limit defined in P1082 within this time.
Notice:
Refer to: P1048, P1082
P1048[0...2] MOP ramp-down time of
the RFG [s]
0.00 -
1000.0
10.00
U, T
-
DDS
Float 2
Sets the ramp-down time for the internal MOP ramp-function generator. The setpoint is changed from limit
defined in P1082 down to zero within this time.
Notice:
Refer to: P1047, P1082
r1050
CO: Actual output freq.
of the MOP [Hz]
-
-
-
-
-
Float 2
Displays output frequency of motor potentiometer setpoint.
P1055[0...2] BI: Enable JOG right
-
19.8
T
-
CDS
U32 /
Bin
3
Defines source of JOG right when P0719 = 0 (Auto selection of command / setpoint source).
P1056[0...2] BI: Enable JOG left
-
0
T
-
CDS
U32 /
Bin
3
Defines source of JOG left when P0719 = 0 (Auto selection of command / setpoint source).
P1057
JOG enable
0000 bin -
0001 bin
0001 bin T
-
-
U16
3
While JOG enable is '0' Jogging (P1056 and P1055) is disabled. When '1' Jogging is enabled.
P1058[0...2] JOG frequency [Hz]
0.00 -
599.00
5.00
U, T
-
DDS
Float 2
Jogging increases the motor speed by small amounts. The JOG mode allows the operator to perform a
specific number of revolutions and position the rotor manually. In JOG mode, the RUN button on the
operator panel for jogging uses a non-latching switch on one of the digital inputs to control the motor
speed. While jogging, P1058 determines the frequency at which the inverter will run. The motor speed is
increased as long as 'JOG left' or 'JOG right' are selected and until the left or right JOG frequency is
reached.