Parameter list
7.2 Parameter list
SINAMICS V20 Inverter
128
Operating Instructions, 07/2012, A5E03728167
Parameter
Function
Range
Factory
default
Can be
changed
Scaling
Data
set
Data
type
Acc.
Level
Bit
Signal name
1 signal
0 signal
00
Fixed frequency Bit 0
Yes
No
01
Fixed frequency Bit 1
Yes
No
02
Fixed frequency Bit 2
Yes
No
03
Fixed frequency Bit 3
Yes
No
04
Inverter data set (DDS) Bit 0
Yes
No
05
Inverter data set (DDS) Bit 1
Yes
No
06
Quick stop disable
Yes
No
08
Enable PID
Yes
No
09
Enable DC brake
Yes
No
13
External fault 1
No
Yes
15
Command data set (CDS) Bit 1
Yes
No
Notice:
r0055 is identical to r2037 if USS is selected as command source via P0700 or P0719.
r0056.0...15 CO / BO: Status of motor
control
-
-
-
-
-
U16
3
Displays status of motor control (in bit format), which can be used to diagnose inverter status.
Bit
Signal name
1 signal
0 signal
00
Init. control finished
Yes
No
01
Motor demagnetizing finished
Yes
No
02
Pulses enabled
Yes
No
03
Voltage soft start select
Yes
No
04
Motor excitation finished
Yes
No
05
Starting boost active
Yes
No
06
Acceleration boost active
Yes
No
07
Frequency is negative
Yes
No
08
Field weakening active
Yes
No
09
Volts setpoint limited
Yes
No
10
Slip frequency limited
Yes
No
11
f_out > f_max Freq. limited
Yes
No
12
Phase reversal selected
Yes
No
13
Imax controller active / torque limit reached
Yes
No
14
Vdc_max controller active
Yes
No
15
KIB (Vdc_min control) active
Yes
No
Notice:
The I-max controller (r0056 bit 13) will be activated when the actual output current (r0027) exceeds the
current limit in r0067.
r0066
CO: Actual output
frequency [Hz]
-
-
-
-
-
Float 3
Displays actual output frequency in Hz. This value is available filtered (r0024) and unfiltered (r0066).
Note:
The output frequency is limited by the values entered in P1080 (minimum frequency) and P1082
(maximum frequency).